Description: The power (P) for point 5 on the Y coordinate of the flow characteristic is saved in p3328. Unit: %
Dependency: Refer to: p3329
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 5 on the X coordinate of the flow characteristic is saved in p3329. Unit: %
Dependency: Refer to: p3328
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The function of the 2-3-WIRE Control Command 1 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
Description: The function of the 2-3-WIRE Control Command 2 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
Description: The function of the 2-3-WIRE Control Command 3 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
p3328[0...n] Fluid flow machine P = f(n), Y coordinate: P flow5 %, point 5 / Fluid flow mach Y5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 100.00
p3329[0...n] Fluid flow machine P = f(n), X coordinate: n flow5 %, point 5 / Fluid flow mach X5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 100.00
p3330[0...n] BI: 2-3-WIRE Control Command 1 / 2-3-WIRE CC_1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3331[0...n] BI: 2-3-WIRE Control Command 2 / 2-3-WIRE CC_2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3332[0...n] BI: 2-3-WIRE Control Command 3 / 2-3-WIRE CC_3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0