Operating Instructions

Communication via PROFIBUS and PROFINET
3.7 Communication via PROFIBUS
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
77
3.7.4.3
Installing the GSD
Procedure
1. Save the GSD on your PC via one of the following methods.
With Internet access:
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Without Internet access:
Insert a memory card into the inverter.
Set p0804 to 12.
The inverter writes the GSD as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.