Description: Sets the setpoint for the input signals in the digital input simulation mode of the PM330 power unit.
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Description: Displays the PROFIenergy mode ID of the effective energy saving mode.
Value: 0: POWER OFF
2: Energy-saving mode 2
255: Ready
Note: Pe: PROFIenergy profiles
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time
- Energy-saving mode, dwell time minimal
Index: [0] = Reserved
[1] = Mode 2
Note: It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operat-
ing state transition time" (system properties).
Pe: PROFIenergy profiles
p4096 PM330 digital inputs simulation mode setpoint / PM330 DI sim setp
CU230P-2_BT
(PM330)
CU230P-2_CAN
(PM330)
CU230P-2_DP
(PM330)
CU230P-2_HVAC
(PM330)
CU230P-2_PN
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.1, external alarm) High Low -
01 DI 1 (X9.2, external fault) High Low -
02 DI 2 (X9.3, Emergency Off category 1) High Low -
03 DI 3 (X9.4, Emergency Off category 0) High Low -
r5600 Pe energy saving mode ID / Pe mode ID
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
300000 [ms] 4294967295 [ms] [0] 300000 [ms]
[1] 480000 [ms]