Operating Instructions
List of parameters
Parameters
1-351
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the communication parameters for CANopen Transmit Process Data Object 3 (TPDO 3).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Notice: For inhibit time and even timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note: Corresponds to the CANopen object 1802 hex.
Transmission types 0, 1 ... F0, FE and FF can be set.
p2048: CANopen sampling time
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Transmit Process Data Object 4 (TPDO 4).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Notice: For inhibit time and even timer, the following apply:
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
Note: Corresponds to the CANopen object 1803 hex.
Transmission types 0, 1 ... F0, FE and FF can be set.
p2048: CANopen sampling time
PDO: Process Data Object
p8722[0...4] CAN Transmit PDO 3 / Transmit PDO 3
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9208, 9210
Min Max Factory setting
0000 hex C000 06DF hex [0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex
p8723[0...4] CAN Transmit PDO 4 / Transmit PDO 4
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9208, 9210
Min Max Factory setting
0000 hex C000 06DF hex [0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex