Operating Instructions

List of parameters
Parameters
1-333
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the weekday on which timer 2 is activated (DTC2).
The switch-on/off time is set in p8421/p8422 and the result displayed via binector output r8423.
Value: 0: Weekday de-activated
1: Weekday activated
Index: [0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency: Refer to: p8409, p8421, p8422, r8423
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the switch on time in hours and minutes for time switch 2 (DTC2).
BO: r8423 = 1 signal:
The condition for the set weekday (p8420) and switch-on time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8420, r8423
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the switch off time in hours and minutes for time switch 2 (DTC2).
BO: r8423 = 0 signal:
The condition for the set weekday (p8420) and switch-off time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8420, r8423
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8420[0...6] RTC DTC2 weekday of activation / RTC DTC2 day act
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p8421[0...1] RTC DTC2 switch-on time / RTC DTC2 t_ON
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 59 0
p8422[0...1] RTC DTC2 off time / RTC DTC2 t_OFF
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 59 0