The time comprises r2114[0] (milliseconds) and r2114[1] (days).
After r2114[0] has reached a value of 86.400.000 ms (24 hours) this value is reset and r2114[1] is incremented.
Index: [0] = Milliseconds
[1] = Days
Dependency: Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
Note: When the electronic power supply is switched out, the counter values are saved.
After the drive unit is powered up, the counter continues to run with the last value that was saved.
Description: Sets the signal source for external alarm 2.
Dependency: Refer to: A07851
Note: An external alarm is triggered with a 1/0 signal.
Description: Sets the signal source for external alarm 3.
Dependency: Refer to: A07852
Note: An external alarm is triggered with a 1/0 signal.
Description: Sets the signal source for external alarm 3.
Dependency: Refer to: A07852
Note: An external alarm is triggered with a 1/0 signal.
Description: Selects faults or alarms for which the message type should be changed.
Dependency: Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Notice: It is not possible to re-parameterize the message type in the following cases:
- if there is no existing message number.
Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the mes-
sage has gone.
p2116[0...n] BI: External alarm 2 / External alarm 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 1
p2117[0...n] BI: External alarm 3 / External alarm 3
PM230
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 1
p2117[0...n] BI: External alarm 3 / External alarm 3
PM330 Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546
Min Max Factory setting
- - 4022.0
p2118[0...19] Sets the message number for message type. / Msg_no Msg_type
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1750, 8075
Min Max Factory setting
0 65535 0