Operating Instructions

Parameters
List of parameters
1-256
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the first signal source to acknowledge faults.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the third signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
p2103[0...n] BI: 1. Acknowledge faults / 1. Acknowledge
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2441, 2442, 2443,
2447, 2475, 2546, 9220, 9677, 9678
Min Max Factory setting
- - [0] 2090.7
[1] 722.2
[2] 2090.7
[3] 2090.7
p2104[0...n] BI: 2. Acknowledge faults / 2. Acknowledge
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - 0
p2104[0...n] BI: 2. Acknowledge faults / 2. Acknowledge
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - [0] 722.2
[1] 0
[2] 0
[3] 0
p2105[0...n] BI: 3. Acknowledge faults / 3. Acknowledge
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - 0