2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
328 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Displays the status of the digital outputs of Power Module 330 (PM330).
Note: DO: Digital Output
Description: Sets the simulation mode for digital inputs of the PM330 power unit.
Dependency: The setpoint for the input signals is specified using p4096.
Refer to: p4096
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Description: Sets the setpoint for the input signals in the digital input simulation mode of the PM330 power unit.
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
r4047 PM330 digital outputs status / PM330 DO status
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X9.8: enable signal UDC link
charged)
High Low -
01 DO 1 (X9.11/X9.12: main contactor control) High Low -
p4095 PM330 digital inputs simulation mode / PM330 DI sim_mode
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) Simulation Terminal eval -
01 DI 1 (X9.4, external fault) Simulation Terminal eval -
02 DI 2 (X9.5, Emergency Off category 0) Simulation Terminal eval -
03 DI 3 (X9.6, Emergency Off category 1) Simulation Terminal eval -
p4096 PM330 digital inputs simulation mode setpoint / PM330 DI sim setp
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -