Operating Instructions

Commissioning
Carrying out basic commissioning
6
67 |
118
Siemens
A5E36496664A_f
Smart Infrastructure 2021-10-11
6. Set the following parameters based on your particular application.
- Minimum speed - factory setting 0 [rpm]
The minimum speed is the lowest speed of the motor independent of the
speed setpoint.
- Maximum speed - factory setting 1500 [rpm]
The converter limits the motor speed to the maximum speed.
- The ramp-up and ramp-down times define the maximum motor
acceleration when the speed setpoint changes. The ramp-up and ramp-
down times are derived from the time between motor standstill and the
maximum speed, or between the maximum speed and motor standstill.
- OFF3 ramp-down time sets the ramp-down time from the maximum speed
down to zero speed for the OFF3 command.