SINAMICS G120 CU230P-2 Control Units
56 List Manual, 04/2018, A5E33838102
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note: The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
For sine-wave filters, the test pulse evaluation to detect short-circuits is always deactivated.
Only motor reactor filter type can be selected for a synchronous reluctance motor (RESM).
If a filter type cannot be selected, then this filter type is not permitted for the power unit.
p0230 = 1:
Power units with output reactor are limited to output frequencies of 150 Hz.
p0230 = 3:
Power units with sine-wave filter are limited to output frequencies of 200 Hz.
Description: Sets the type of the filter at the motor side.
Value: 0: No filter
1: Motor reactor
2: dv/dt filter
Dependency: The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note: If a filter type cannot be selected, then this filter type is not permitted for the power unit.
p0230 = 1:
Power units with output reactor are limited to output frequencies of 150 Hz.
Description: Displays the maximum permissible cable lengths between the drive unit and motor.
Index: [0] = Unshielded
[1] = Shielded
Note: The display value is used to provide information for service and maintenance.
Description: Enter the inductance of a filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note: When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
p0230 Drive filter type motor side / Drv filt type mot
PM330 Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1, 2) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 2 0
r0231[0...1] Power cable length maximum / Cable length max
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [m] - [m] - [m]
p0233 Power unit motor reactor / PU mot reactor
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 2), U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [mH] 1000.000 [mH] 0.000 [mH]