Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
202 List Manual, 04/2018, A5E33838102
Note: For bit 04:
Field orientation for the closed-loop control of application class Standard Drive Control (p0096 = 1). The field
orientation is activated with the automatic calculation if p0096 is set = 1.
For bit 05 (only effective for p1302.4 = 1):
The starting current when accelerating (p1311) generally results in an increase in the absolute current and flux. With
p1302.5 = 1 the current is only increased in the direction of the load. p1302.5 - in conjunction with p1310 and p1311
- are decisive when it comes to defining the quality of the starting response.
For bit 07:
For field orientation (bit04 = 1), an Iq,max controller supports the current limiting controller (see p1341). Inhibiting the
integral component can prevent the drive from stalling under overload conditions.
For bit 08:
Taking into account the saturation characteristic can be activated to improve faster starting operations for high-rating
motors.
For bit 09:
For field orientation (bit04 = 1), while the induction motor is being magnetized, the current is automatically increased
if the magnetization time p0346 is shortened.
Description: Defines the voltage boost as a [%] referred to the rated motor current (p0305).
The magnitude of the permanent voltage boost is reduced with increasing frequency so that at the rated motor
frequency, the rated motor voltage is present.
The magnitude of the boost in Volt at a frequency of zero is defined as follows:
Voltage boost [V] = 1.732 x p0305 (rated motor current [A]) x r0395 (stator/primary section resistance [ohm]) x p1310
(permanent voltage boost [%]) / 100 %
At low output frequencies, there is only a low output voltage in order to maintain the motor flux. However, the output
voltage can be too low in order to achieve the following:
- magnetize the induction motor.
- hold the load.
- compensate for losses in the system.
This is the reason that the output voltage can be increased using p1310.
The voltage boost can be used for both linear as well as square-law U/f characteristics.
Dependency: The starting current (voltage boost) is limited by the current limit p0640.
Only for p1302.4 = 0 (no field orientation):
The accuracy of the starting current depends on the setting of the stator and feeder cable resistance (p0350, p0352).
For vector control, the starting current is realized using p1610.
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1300, p1311, p1312, r1315
Notice: The starting current (voltage boost) increases the motor temperature (particularly at zero speed).
Note: The starting current as a result of the voltage boost is only effective for U/f control (p1300).
The boost values are combined with one another if the permanent voltage boost (p1310) is used in conjunction with
other boost parameters (acceleration boost (p1311), voltage boost for starting (p1312)).
However, these parameters are assigned the following priorities: p1310 > p1311, p1312
p1310[0...n] Starting current (voltage boost) permanent / I_start (Ua) perm
PM230
PM250, PM260
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6300, 6301
Min Max Factory setting
0.0 [%] 250.0 [%] 50.0 [%]