Operating Instructions
List of Parameters
Parameters
1-355
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note: Corresponds to the CANopen object 1400 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note: Corresponds to the CANopen object 1401 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 3 (RPDO 3).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note: Corresponds to the CANopen object 1402 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8700[0...1] CAN Receive PDO 1 / Receive PDO 1
CU230P-2 CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex
p8701[0...1] CAN Receive PDO 2 / Receive PDO 2
CU230P-2 CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex
p8702[0...1] CAN Receive PDO 3 / Receive PDO 3
CU230P-2 CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex