Operating Instructions

Communication over CANopen
6.3 PDO services
Fieldbuses
184 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
6.3.2
Free PDO mapping
Using the free PDO mapping, you configure and interconnect any process data as required
as follows:
as free objects
free objects (Page 203) or
as objects of drive profile CiA 402, corresponding to the requirements of your system for
the PDO service
The precondition is that the inverter is set for free PDO mapping. (p8744 = 2) (factory
setting).
Configuring and mapping process data using free PDO mapping
Procedure
1. Specify the process data.
Examples:
Send current actual value (r0068) from the inverter to the controller (TPDO - Transmit
Process Data Object)
Send additional speed setpoint from the controller to the inverter (RPDO - Receive
Process Data Object) and write in p1075
2. Specify objects for transmission of the process data
TPDO1 for the current actual value
RPDO1 for additional speed setpoint
3. Define the communication parameters for RPDO and TPDO
Define communication parameters for RPDO.
RPDO communication parameters (Page 196)
Define communication parameters for TPDO.
See TPDO communication parameters (Page 199)
4. Select the OV index for the mapping parameters
Mapping parameters for RPDO.
RPDO mapping parameters (Page 197)
Mapping parameters for TPDO.
TPDO mapping parameters (Page 201)
5. Write OV index into the SINAMICS mapping parameters
p8710 … p8717 for RPDO
p8730 … p8737 for TPDO