Connecting
5.3 Connecting the line and motor cable at the inverter
PM230 Power Module, IP55
Hardware Installation Manual, 12/2016, A5E35319202B AB
35
2. Remove the cable gland plate from the bottom of the inverter.
Diameters of the drill holes in the cable gland plates:
20.5 mm
Control cables
20.5 mm
Mains and motor cables, FSA
25.5 mm
Mains and motor cables, FSB
32.5 mm
Mains and motor cables, FSC
Figure 5-3 Bolting plates for PM230, FSA to FSC
3. Prepare the mains and motor cables for connection in accordance with the table below.
Inverter
Connection
Dimensions
Explanation
A
B
C
1)
D
FSA
Mains cable
10 mm
60 mm
-
90 mm
Motor cable
10 mm
60 mm
10 mm
60 mm
FSB
Mains cable
10 mm
60 mm
-
50 mm
Motor cable
10 mm
50 mm
10 mm
40 mm
FSC
Mains cable
10 mm
50 mm
-
70 mm
Motor cable 10 mm 50 mm 10 mm 40 mm
1)
Cable shield
① Bolting plate
4. Assemble the cable glands with the prepared cables and EMC cable glands for the
control cables.
5. Seal any unused bushings with a rubber sleeve.
6. Secure the bolting plate to the inverter enclosure. Tightening torque: 2 Nm
Make sure that the seal of the bolting plate is not damaged.