Installation Instructions

Table Of Contents
PM230 Power Module, IP55
Hardware Installation Manual, 12/2016, A5E35319202B AB
19
Installing/mounting
4
4.1
Installation conditions
General installation conditions
When installing the Power Modules, carefully observe the following sections in
Chapter
Technical data (Page 47) in order to guarantee reliable, continuous and
disturbance-free operation.
Cable cross-sections and tightening torques
Electromagnetic compatibility
Ambient conditions
General technical specifications
The permissible fuses, power loss and the required cooling air quantities are listed in the
specific technical specifications.
The EMC-compliant connection is described in Section:
EMC compliant installation of a machine or system (Page 21).
The Power Module is intended for wall mounting. If the
Power Module is not mounted on a wall, the rear panel of
the heat sink must be covered with a plate.
Do not expose the inverter to direct sunlight.
To comply with protection class IP55,
either an operator
panel or a dummy cover is required for operating the inver
t-
er.
"Installing the operator panel or dummy cover
(Page
28)".