Operating Instructions
List of Parameters
Parameters
1-77
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the system response when the motor temperature reaches the alarm threshold.
Value: 0: No response only alarm no reduction of I_max
1: Alarm with reduction of I_max and fault
2: Alarm and fault no reduction of I_max
Dependency: Refer to: p0601, p0604, p0605
Refer to: F07011, A07910
Note: The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
If value = 0:
p0606 is not started, therefore only alarm A07910 is output.
If value = 1:
PTC: Same as value = 2 because there is no reduction in I_max.
KTY84: Alarm A07910 is output, I_max is reduced and p0606 is started. After p0606 has elapsed, fault F0711 is
set.
If value = 2:
Alarm A07910 is output and p0606 is started. After p0606 has elapsed, fault F0711 is set.
Description: Sets the system response when the motor temperature reaches the alarm threshold.
Value: 0: No response only alarm no reduction of I_max
1: Alarm with reduction of I_max and fault
2: Alarm and fault no reduction of I_max
Dependency: Refer to: p0601, p0604, p0605
Refer to: F07011, A07910
Note: The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
If value = 0:
p0606 is not started, therefore only alarm A07910 is output.
If value = 1:
PTC: Same as value = 2 because there is no reduction in I_max.
KTY84: Alarm A07910 is output, I_max is reduced and p0606 is started. After p0606 has elapsed, fault F0711 is
set.
If value = 2:
Alarm A07910 is output and p0606 is started. After p0606 has elapsed, fault F0711 is set.
p0610[0...n] Motor overtemperature response / Mot temp response
CU230P-2 BT Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0 2 2
p0610[0...n] Motor overtemperature response / Mot temp response
CU230P-2 CAN
CU230P-2 DP
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0 2 1