Operating Instructions

Parameters
List of Parameters
1-348
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle time is 100 ms.
When a 0 is written, then heartbeat telegrams are not sent.
Dependency: Only adjustable if guard time = 0 (node guarding disabled).
Refer to: p8604
Note: Corresponds to the CANopen object 1017 hex.
Either node guarding or heartbeat can be used.
Description: General device information display.
Index: [0] = Vendor ID
[1] = Product code
[2] = Revision number
[3] = Serial number
Note: Corresponds to the CANopen object 1018 hex.
Re index 3:
The SINAMICS serial number comprises 60 bits. Of these bits, the following are displayed in this index:
Bits 0 ... 19: Consecutive number
Bits 20 ... 23: Production ID
- 0 hex: Development
- 1 hex: P1 unique number
- 2 hex: P2 unique number
- 3 hex: WA unique number
- 9 hex: Pattern
- F hex: All others
Bits 24 ... 27: Month of manufacture (0 means January, B means December)
Bits 28 ... 31: Year of manufacture (0 means 2002)
p8606 CAN Producer Heartbeat Time / Prod Heartb Time
CU230P-2 CAN Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 65535 [ms] 0 [ms]
r8607[0...3] CAN Identity Object / Identity object
CU230P-2 CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -