Installation Instructions

FSB
One grey ferrite
for the line cable
Blue ferrite for the
motor cable
FSC
Two grey ferrites
for the line cable
Blue ferrite for the
motor cable
FSA
Blue ferrite for the
motor cable
0
I
LO
I
1.5 * I
LO
1.1 * I
LO
3 s 57 s 240 s
300 s
t[s]
Load cycle 300 s based on
Low Overload
0
I
HO
I
2 * I
HO
1.1 * I
HO
3 s 57 s 240 s
300 s
t[s]
Load cycle 300 s based on
High Overload
Compact Operating Instructions
SINAMICS G120
Power Module PM230 FSA ... FSC, IP55
LO base load values
HO base load values
Rated
input
current
Frame
Size
Order No.
*)
Line fuses
Power
Output
current
Power
Output
current
Acc. To IEC,
e.g. Siemens
UL,
J type
kW
hp
A
kW
hp
A
A
0.37
0.5
1.3
0.25
0.34
0.9
1.3
FSA
6SL3223-0DE13-7_A1
3NA3803
10 A
0.55
0.75
1.7
0.37
0.5
1.3
1.8
FSA
6SL3223-0DE15-5_A1
3NA3803
10 A
0.75
1
2.2
0.55
0.75
1.7
2.3
FSA
6SL3223-0DE17-5_A1
3NA3803
10 A
1.1
1.5
3.1
0.75
1
2.2
3.2
FSA
6SL3223-0DE21-1_A1
3NA3803
10 A
1.5
2
4.1
1.1
1.5
3.1
4.2
FSA
6SL3223-0DE21-5_A1
3NA3803
10 A
2.2
3
5.9
1.5
2
4.1
6.1
FSA
6SL3223-0DE22-2_A1
3NA3803
10 A
3
4
7.7
2.2
3
5.9
8
FSA
6SL3223-0DE23-0_A1
3NA3803
10 A
4
5.4
10.2
3
4
7.7
10.5
FSB
6SL3223-0DE24-0_A1
3NA3805
16 A
5.5
7.4
13.2
4
5.4
10.2
13.6
FSB
6SL3223-0DE25-5_A1
3NA3807
25 A
7.5
10
18
5.5
7.4
13.2
18.6
FSB
6SL3223-0DE27-5_A1
3NA3810
35 A
11
14.75
26
7.5
10
18
26.9
FSC
6SL3223-0DE31-1_A1
3NA3814
40 A
15
20
32
11
14.75
26
33.1
FSC
6SL3223-0DE31-5_A1
3NA3820
50 A
18.5
25
38
15
20
32
39.2
FSC
6SL3223-0DE31-8AA1
3NA3820
50 A
*)
_: A = filter class A unit, B = filter class B
Ferrite rings to fulfill the EMI Standard C1 for conducted emissions
To fulfill the EMI Standard C1 for conducted emissions a Power Module with a class B filter is required.
In addition the blue ferrite must be attached to the motor cable between the screening and the terminals as shown in the figures.
Furthermore for FSB and FSC the grey ferrites must be attached to the line supply cable as shown in the figures.
Cable lengths, using
Cable type
EMC category
filtered units, class A
screened
second environment, C2
25 m
second environment, C3
50 m
unscreened
none
100 m
filtered units, class B
screened
first environment, C1 (conducted emissions only)
25 m *)
second environment, C2
50 m
unscreened
none
100 m
*) To fulfill the EMI standard C1 for conducted emissions, use ferrite rings as shown in the figures below
Feature Specification
Line voltage
3 AC 380 V … 480 V ± 10 % up to 2000 m (6600 ft) installation altitude.
Output voltage
3 AC 0 V … input voltage * 0.95
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 Hz … 550 Hz, depending on the control mode
Power factor λ
0.9
Inrush current
Less than rated input current
Pulse frequency (factory setting)
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
Electromagnetic compatibility
The Power Module complies with the following EMC emission requirements at the default settings of the Power Module.
Conducted emissions: The devices are suitable for second environment category C1 and C2 in accordance with IEC61800-3.
R
adiated Emissions: The devices are suitable for second environment category C2
Electromagnetic compatibility
The devices comply with EN 61800-3: 2004 suitable for Category C1 and C2 environments.
Braking methods
DC braking
Environmental rating
IP55 / UL Type 12
Motor overload protection
This equipment is capable of providing internal motor overload protection according to UL508C. The protection level is 115 %, 230 %
and 400 % full load current of the equipment. This is adjusted via parameter p0640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
LO Operation temperature
*)
-10 °C … 40 °C (32 °F … 104 °F) without current derating / up to 60 °C (140 °F) with current derating
HO Operating temperature
*)
-10 °C … 50 °C (32 °F … 122 °F) without current derating / up to 60 °C (140 °F) with current derating
Storage temperature
- 40 °C … +70 °C (- 40 °F … 158 °F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
Humidity
< 95% RH - non-condensing
Environmental conditions
Suitable for environmental class 3C2 according to IEC 60721-3-3 against damaging chemical substances
Pollution
Protected from contact with dangerous parts, dust, spray water and water jets
Shock
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1 : Transport in the transport packaging according
to Class 2M3 of IEC 60721-3-2. Operation according to Class 3M2. See Hardware Installation Manual for detailed specifications.
Vibration
Long-term storage in the transport packaging according to Class 1M2 to IEC 60721-3-1 : Transport in the transport packaging according
to Class 2M3 to IEC 60721-3-2. Operation according to Class 3M2. See Hardware Installation Manual for detailed specifications.
Line impedance
With Uk 1 %, a line reactor must not be used
Short Circuit Current Rating (SCCR)
Suitable for use on a circuit capable of delivering not more than 40 kA rms symetrical amperes; 480 Vac maximum when protected by
Class J or R/C (JFHR2) semiconductor fuses only as stated
*)
according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all.
T
he maximum temperature is determined by the component (Power Module, Control Unit or Operator panel) with the lowest maximum temperature
C
AUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
Ferrite rings to fulfill the EMI Standard C2
To fulfill the EMI Standard C2 for the Power Modules FSB and FSC, one grey
ferrite must be attached to the line supply cable. A ferrite for the motor cable is
not required.
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use UL/cUL-
certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
Transient surge suppression must be installed on the line side of this equipment. We recommend a VZCA7 circuit
breaker type rated at the following specifications: 480 V (phase to ground), 480 V (phase to phase), suitable for overvol-
tage category III, provides protection for a VPR maximum of 2 kV and type 1 or type 2 SPD application.