Operating Instructions
Communication via RS485
5.4 Communication using Modbus RTU
Fieldbuses
132 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Table 5- 11 Assigning the Modbus register to the parameters - process data
Regis-
ter
Description
Access
Scaling
Data / parameter
40100 Control word
You can find details in function
chart 9342 in the List Manual of
the inverter.
Manuals (Page 232)
R/W 1 Process data 1
40101
Main setpoint
R/W
1
Process data 2
40110 Status word
You can find details in function chart
9352 in the List Manual of
the inverter.
Manuals (Page 232)
R 1 Process data 1
40111
Main actual value
R
1
Process data 2