Operating Instructions

Commissioning
Additional settings
6
77 |
118
Siemens
A5E36496664A_f
Smart Infrastructure 2021-10-11
6.6.3 Overview of parameters
Open the Parameters menu
Selection of the Parameters menu on BOP-2 and IOP-2-BT
Table 12: Parameter selection
Overview of parameters
The table below contains only an excerpt from the parameter list. You can find a
complete list of parameters in List Manual CU230P, SIOS Entry-ID: 109782303.
Parameter Factory
settings
Function
p0601 0 Motor temperature sensor type:
0: No sensor
1: PTC warning & timer
2: KTY84
4: Bimetallic NC contact warning & timer
6: Pt 1000
p0730 r52.3 Digital output 0: Fault active
p0731 r52.7 Digital output 1: Alarm active
p0732 r52.2 Digital output 2: Operation enabled. Motor in operation.
p0748 000 Invert digital outputs (0 = do not invert, 1 = invert)
Bit 0: DO 0
Bit 1: DO 1
Bit 2: DO 2
r0755[0..3] - Analog inputs, actual value in percent