1. Expose the shield around the length C in order to ensure that devices with an
EMC filter of Class B conform to EMC category C1.
2. When the cable is fed through the base plate, also expose the shield around
the length D (see sketch above, at the end of "D") and insert the cable through
the conductively connected EMC cable gland.
5.3.2.3 Connecting line and motor terminals
Instructions on how to connect line and motor terminals are given below:
For IP20 devices, follow the instructions in Chapter IP20 devices [ 38]
devices.
For IP55 devices, follow the instructions in Chapter IP55 devices [ 40]
devices.
In addition to the information below, please also read Chapter EMC-compliant
installation (examples) [ 47].
IP20 devices
Overview
Figure 12: Connection of G120P IP20
Item Designation
1
Line filter (filter B only)
2
Power Module
3
Sine-wave filter (optional)
NOTICE
Scope of supply for IP20
A screening termination kit for the Power Module PM230 is included with the IP20
devices in frame sizes A to C. For frame sizes D to F, the screening termination
kit must be ordered separately if required.
1
2
3
Cable preparation