Operating Instructions

Service, maintenance and fault rectification
Fault rectification
8
106 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
How to proceed if a fault is discovered
The variable speed drive has failed one of these tests:
Remove the Power Module (power unit) in order to replace or repair it.
A short circuit is present at the input rectifiers or at components of the IGBT
bridge:
Check the state of fuses in the supply line, of contactors, disconnectors or of
the motor itself.
Remember that an apparently open circuit can also occur following a component
short-circuit and the resulting strong flow of current.