Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
521
2 Parameters
2.2 List of parameters
For p31020 = 1:
The following BICO interconnections are automatically established:
- p31023[0] = r0755[0]
- p31023[2] = r0755[1]
- p31026[0] = r0755[2]
- p31026[1] = r0755[3]
- p2253[0] = r31024
- p2264[0] = r31027
Description: Sets the configuration for multi-zone control.
Value: 0: Setpoint 1 / multiple actual values
1: Two zones / highest value setting
2: Two zones / lowest value setting
Note: For p31021 = 0:
The setpoint 1 and the output of the actual value processing are forwarded to the technology controller.
For p31021 = 1:
The highest value setting ensures that the actual values of the two zones remain below their respective setpoint.
For p31021 = 2:
The lowest value setting ensures that the actual values of the two zones remain above their respective setpoint.
Description: Sets the processing method for the multi-zone control actual value (r31027).
Value: 0: Only actual value 1
1: Only actual value 2
2: Only actual value 3
3: Difference (actual value 1, 2)
4: Sum (actual value 1, 2)
5: Sum (actual value 1, 2 and 3)
6: Mean value (actual value 1, 2)
7: Mean value (actual value 1, 2 and 3)
8: Minimum (actual value 1, 2)
9: Minimum (actual value 1, 2 and 3)
10: Maximum (actual value 1, 2)
11: Maximum (actual value 1, 2 and 3)
Note: For p31022 = 0, 1, 2:
Only actual value 1, 2, or 3 is used as r31027.
For p31022 = 3:
The difference between actual values 1 and 2 is used as r31027.
For p31022 = 4:
The sum of actual values 1 and 2 is used as r31027.
For p31022 = 5:
The sum of actual values 1, 2, and 3 is used as r31027.
For p31022 = 6:
The mean value of actual values 1 and 2 is used as r31027.
p31021 Multi-zone control configuration / Zone_ctrl config
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 2 0
p31022 Multi-zone control for actual value processing / Zone_ctrl act proc
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 11 0