Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
365
2 Parameters
2.2 List of parameters
Description: Display and connector output for the status word of the DC quantity control.
Dependency: Refer to: p3856
Description: Display and connector output for the status word of the compound braking and DC quantity control.
Dependency: Refer to: p3856
Description: Sets the signal source to activate the essential service mode (ESM) via digital input.
Using this function, when required the motor can be operated for as long as possible (e.g. to extract smoke).
BI: p3880 = 1 signal:
The essential service mode is activated.
BI: p3880 = 0 signal:
The essential service mode is deactivated.
Dependency: Refer to: p3881, p3882, p3883, p3884, r3887, p3888, r3889
Warning: When activating the essential service mode (BI: p3880 = 1 signal), the motor immediately runs according to the
selected setpoint source. When the essential service mode is activated, the motor cannot be stopped using the OFF
commands.
Note: ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 5, 11, 12
r3859.1 CO/BO: DC quantity control status word / DC_ctrl ZSW
PM230 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6797
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 DC quantity control active in the
overmodulation range
Yes No -
r3859.0...1 CO/BO: Compound braking/DC quantity control status word / Comp-br/DC_ctr ZSW
PM240 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6797
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Compound braking active Yes No -
01 DC quantity control active in the
overmodulation range
Yes No -
p3880 BI: ESM activation signal source / ESM act s s
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
- - 0