Operating Instructions
List of parameters
Parameters
1-303
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
Description: Sets a fixed percentage.
Dependency: Refer to: p2900, p2930
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
Description: Signal sources for frequently used percentage values.
Index: [0] = Fixed value +0 %
[1] = Fixed value +5 %
[2] = Fixed value +10 %
[3] = Fixed value +20 %
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency: Refer to: p2900, p2901, p2930
Note: The signal sources can, for example, be used to interconnect scalings.
Description: Sets a fixed value for torque.
Dependency: Refer to: p2900, p2901
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can, for example, be used to interconnect a supplementary torque.
p2901[0...n] CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]
r2902[0...14] CO: Fixed values [%] / Fixed values [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
- [%] - [%] - [%]
p2930[0...n] CO: Fixed value M [Nm] / Fixed value M [Nm]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2003 Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
-100000.00 [Nm] 100000.00 [Nm] 0.00 [Nm]