Notice: Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note: Re bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output
voltage).
Re bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
Re bit 01 = 0:
DC link voltage compensation in the modulator.
Re bit 01 = 1:
DC link voltage compensation in the current control.
Description: Sets the configuration for the modulator.
Notice: Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note: Re bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output
voltage).
Re bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
Re bit 01 = 0:
DC link voltage compensation in the modulator.
Re bit 01 = 1:
DC link voltage compensation in the current control.
Description: Sets the phase sequence reversal for the motor without setpoint change.
If the motor does not rotate in the required direction, then the output phase sequence can be reversed using this
parameter. This means that the direction of the motor is reversed without the setpoint being changed.
Value: 0: OFF
1: ON
Note: This setting can only be changed when the pulses are inhibited.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for U_lim (only for
Vdc_comp. in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -
p1810 Modulator configuration / Modulator config
PM240 Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for U_lim (only for
Vdc_comp. in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -
p1820[0...n] Reverse the output phase sequence / Outp_ph_seq rev
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(2), T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0