Description: Displays the status of the motor model.
Description: Sets the speed to change over the motor model to encoderless operation.
Dependency: Refer to: p1756
Notice: The changeover speed represents the steady-state minimum speed up to which the motor model can be used
in steady-state operation without encoder.
If the stability is not adequate close to the changeover speed, it may make sense to increase the parameter value.
Note: The changeover speed applies for the changeover between open-loop and closed-loop control mode.
Description: Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
Dependency: Refer to: p1755
Note: The parameter value refers to p1755.
r1751 Motor model status / MotMod status
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Controlled operation Active Inactive 6721
01 Set ramp-function generator Active Inactive -
02 Stop RsLh adaptation Yes No -
03 Feedback Active Inactive -
05 Holding angle Yes No -
06 Acceleration criterion Active Inactive -
07 Set angular integrator PEM No Yes -
08 Stop Kt adaptation PEM No Yes -
09 PolID active PEM SLVC No Yes -
10 I injection PEM No Yes -
11 Speed controller output cannot be set to
zero
Yes No -
12 Rs adapt waits Yes No -
13 Motor operation Yes No -
14 Stator frequency sign Positive Negative -
15 Torque sign Motor mode Regenerative mode -
16 Pulse injection active PEM Yes No -
17 Operation with feedback Selected Deselected -
p1755[0...n] Motor model changeover speed encoderless operation / MotMod n_chgSnsorl
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 210000.00 [rpm]
p1756 Motor model changeover speed hysteresis encoderless operation /
MotMod n_chgov hys
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.0 [%] 95.0 [%] 50.0 [%]