Operating Instructions

Number Cause Remedy
F13100 Know-how protection: Copy protec‐
tion error
The know-how protection and the copy protection for the memory card are
active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the inverter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec‐
tion cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
V/f operation: Assignment of rated currents of motor and Power Module
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
V/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
F30003 DC-link voltage undervoltage Check the line voltage (p0210).
F30004 Inverter overtemperature Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
F30005 I2t inverter overload Check the rated currents of the motor and Power Module.
Reduce the current limit p0640.
When operating with V/f characteristic: Reduce p1341.
F30011 Line phase failure Check the inverter's input fuses.
Check the motor feeder cables.
F30015 Motor cable phase failure Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
F30021 Ground fault
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
Alarms, faults and system messages
8.6 List of alarms and faults
Converter with the CU230P-2 Control Units