Default setting 112: "CO2 sensor, 2 PID setpoints"
&2VHQVRU99ฬ
)L[HGYDOXH
)L[HGYDOXH
6SHHGDFWXDOYDOXH
&XUUHQWDFWXDOYDOXH
$ODUP
)DXOW
2SHUDWLRQ
7HFKQRORJ\FRQWUROOHU
6SHHGVHWSRLQW
)L[HGYDOXHRU
212))
$,
',
',


$2
$2

'2



'2



'2


ุ
&2
DO 0: p0730, …,
DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0, DI 2: r0722.2 AI 0: r0755[0]
Additional settings:
CO
2
control using the technology controller
Analog inputs smoothing time constant: p0753 = 500 ms
Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
Default setting of the technology controller:
Enable: p2200 = 1
Fixed value 1: p2201 = 50 %
Fixed value 3: p2203 = 10 %
Technology controller setpoint 1: p2253 = r2224 (active fixed value)
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
Actual value filter time constant: p2265 = 10 s
Technology controller system deviation inversion: p2306 = 1
"Flying restart" is enabled: p1200 = 1
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in the BOP-2: P_F_CO2
Installing
4.5 Connecting the interfaces for the inverter control
Converter with the CU230P-2 Control Units
134 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF