Operating Instructions
List of parameters
Parameters
1-177
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the integral time for the Vdc controller (DC link voltage controller).
Description: Sets the rate time constant for the Vdc controller (DC link voltage controller).
Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller. When the sensing
function is de-activated, the activation threshold r1282 for the Vdc_max controller is determined from the parame-
terized connection voltage p0210.
Value: 0: Automatic detection inhibited
1: Automatic detection enabled
Description: Sets the time threshold for the Vdc_min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized.
Prerequisite: p1296 = 1
Notice: If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1280 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the
event of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
Description: Sets the response for the Vdc_min controller (kinetic buffering).
Value: 0: Buffer Vdc until undervoltage, n<p1297 -> F07405
1: Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
p1291[0...n] Vdc controller integral time (U/f) / Vdc_ctrl Tn
PM230
PM240, PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 10000 [ms] 40 [ms]
p1292[0...n] Vdc controller rate time (U/f) / Vdc_ctrl t_rate
PM230
PM240, PM330
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 1000 [ms] 10 [ms]
p1294 Vdc_max controller automatic detection ON signal level (U/f) / Vdc_max SenseOnLev
PM230
PM240, PM330
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p1295[0...n] Vdc_min controller time threshold (U/f) / Vdc_min t_thresh
PM240
PM330
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 10000.000 [s] 0.000 [s]
p1296[0...n] Vdc_min controller response (kinetic buffering) (U/f / Vdc_min response
PM240
PM330
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0