Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
132 List Manual, 04/2018, A5E33838102
Description: Sets the main contactor holding time after OFF1
Dependency: Refer to: p0869
Note: After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switching on inhibited must be
acknowledged via the source of p0840 = 0 (OFF1) – and before the main contactor holding time expires, should go
back to 1, otherwise the main contactor will open.
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
Description: Sets the debounce time for the DC circuit breaker for power units in the "chassis" format.
Note: The following applies if p0868 = 65000 ms:
The debounce time defined internally in the power unit's EEPROM is implemented.
Description: Sets the configuration for the sequence control.
Dependency: Refer to: p0867
Note: For bit 00:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching on inhibited must be acknowledged via the source of p0840 =
0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the main
contactor will open.
Description: Sets the signal source to close the main contactor.
Note: The main contactor is also closed when the converter is switched on after issuing the necessary enable signals. A
binector input p0870 = 1 signal prevents the main contactor from being opened when enable signals are withdrawn.
p0867 Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [ms] 500.0 [ms] 50.0 [ms]
p0868 Power unit thyristor rectifier wait time / PU thy_rect t
PM330 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 65000 [ms] 0 [ms]
p0869 Sequence control configuration / Seq_ctrl config
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Keep main contactor closed for STO Yes No -
p0870 BI: Close main contactor / Close main cont
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0