Operating Instructions

Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
159
Multi-State Input Objects
Instance
ID
Object name
Description
Possible values
Access type
Parameter
MSI0
FAULT_1
Fault number 1
See List Manual "List of faults and
alarms"
R
r0947[0]
MSI1 FAULT_2 Fault number 2 R r0947[1]
MSI2
FAULT_3
Fault number 3
R
r0947[2]
MSI3
FAULT_4
Fault number 4
R
r0947[3]
MSI4
FAULT_5
Fault number 5
R
r0947[4]
MSI5
FAULT_6
Fault number 6
R
r0947[5]
MSI6
FAULT_7
Fault number 7
R
r0947[6]
MSI7
FAULT_8
Fault number 8
R
r0947[7]
MSI8 WARNING_1 Warning num-
ber 1
R r2110[0]
MS9 WARNING_2 Warning num-
ber 2
R r2110[1]
MSI10 WARNING_3 Warning num-
ber 3
R r2110[2]
MSI11 WARNING_4 Warning num-
ber 4
R r2110[3]
MSI12 WARNING_5 Warning num-
ber 5
R r2110[4]
MSI13 WARNING_6 Warning num-
ber 6
R r2110[5]
MSI14 WARNING_7 Warning num-
ber 7
R r2110[6]
MSI15 WARNING_8 Warning num-
ber 8
R r2110[7]