Fig. 2-89 7030 – Free technology controller 0, 1, 2
- 7030 -
Function diagram
87654321
fp_7030_97_01.vsd
Technology functions
G120 CU230P-2
12.12.2012 V4.6
Free Technology controller 0, 1, 2
d
dt
Ftec0 D comp T
0.000 ... 60.000 [s]
p11074 (0.000)
Ftec0 act v T
0.00 ... 60.00 [s]
p11065 (0.00)
Ftec0 act v s_s
(0)
p11064
x
y
Ftec0 act v up lim
-200.00 ... 200.00 [%]
p11067 (100.00)
Ftec0 act v inv
0 ... 1
p11071 (0)
r11072
Ftec0 act v af lim [%]
-1
Ftec0 stat_word
r11049
r11049
.10
Ftec0 stat_word
r11049
r11049
.11
r11094
Ftec0 out_sig
[%]
+
+
+
+
Ftec0 setp s_s
(0)
p11053
Ftec0 setp t_r-up
0.00 ... 650.00 [s]
p11057 (1.00)
Ftec0 setp t_r-dn
0.00 ... 650.00 [s]
p11058 (1.00)
r11073
Ftec0 sys dev [%]
(0)
Ftec0 enab
p11000
Ftec0 lim max s_s
(11091[0])
p11097
Ftec0 lim min s_s
(11092[0])
p11098
Ftec0 lim r-u/r-dn
0.00 ... 100.00 [s]
p11093 (1.00)
Ftec0 lim max
-200.00 ... 200.00 [%]
p11091 (100.00)
Ftec0 lim min
-200.00 ... 200.00 [%]
p11092 (0.00)
Ftec0 lim offs
(0)
p11099
1
Ftec0 stat_word
r11049
r11049
.0
<1> P, I and D components can be disabled by entering a zero.
Ftec0 Tn
0.000 ... 10000.000 [s]
p11085 (30.000)
Ftec0 Kp
0.000 ... 1000.000
p11080 (1.000)
r11060
Ftec0 setp aft
RFG [%]
Free Technology Controller
F07436
0 :
Free Technology Controller 1 :
Free Technology Controller 2 :
Ftec0 act v lo lim
-200.00 ... 200.00 [%]
p11068 (-100.00)
p11000 to p11099 (pictured in this FP)
p11100 to p11199
p11200 to p11299
<1><1>
<2>
<2> Free Technology Controller 1: F07437,
Free Technology Controller 2: F07438
Ftec0 t_samp
0 ... 4
p11028 (2)
<1>