Operating Instructions

Parameters
List of parameters
1-464
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Re p31021 = 2:
The lowest value setting ensures that the actual values of the two zones remain above their respective setpoint.
Description: Sets the processing method for the multi-zone control actual value (r31027).
Value: 0: Only act 1
1: Only act 2
2: Only act 3
3: Difference (actual value 1, 2)
4: Sum (actual value 1, 2)
5: Sum (actual value 1, 2 and 3)
6: Mean value (actual value 1, 2)
7: Mean value (actual value 1, 2 and 3)
8: Minimum (actual value 1, 2)
9: Minimum (actual value 1, 2 and 3)
10: Maximum (actual value 1, 2)
11: Maximum (actual value 1, 2 and 3)
Note: Re p31022 = 0, 1, 2:
Only actual value 1, 2, or 3 is used as r31027.
Re p31022 = 3:
The difference between actual values 1 and 2 is used as r31027.
Re p31022 = 4:
The sum of actual values 1 and 2 is used as r31027.
Re p31022 = 5:
The sum of actual values 1, 2, and 3 is used as r31027.
Re p31022 = 6:
The mean value of actual values 1 and 2 is used as r31027.
Re p31022 = 7:
The mean value of actual values 1, 2 and 3 is used as r31027.
Re p31022 = 8:
The lower value of actual values 1 and 2 is used as r31027.
Re p31022 = 9:
The lowest value of actual values 1, 2, and 3 is used as r31027.
Re p31022 = 10:
The higher value of actual values 1 and 2 is used as r31027.
Re p31022 = 11:
The highest value of actual values 1, 2, and 3 is used as r31027.
Description: Sets the signal source for the multi-zone control setpoints.
p31022 Multi-zone control for actual value processing / Zone_ctrl act proc
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 11 0
p31023[0...3] CI: Multi-zone control setpoint input / Zone_ctrl setp inp
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0