Technical data
7.9 Electromagnetic compatibility of variable-speed drives
PM230 Power Module, IP55
Hardware Installation Manual, 12/2016, A5E35319202B AB
61
7.9.1
Inverter applications
Inverters involve equipment used on a professional basis, deployed in certain areas of
business and industry - and are not operated in the general public domain.
For an EMC-compliant installation, observe the information provided in the Configuration
manual: EMC installation guideline
(http://support.automation.siemens.com/WW/view/en/60612658).
The Power Modules described here are intended for operation in the first and second
environments. Conditions for operation in the respective environment are subsequently
listed.
7.9.2
Operation in the Second Environment
Interference immunity
You do not have to take any additional measures regarding interference immunity.
Interference emission - operation in the second environment, Category C2
The drive system must comply with the following conditions in order to comply with the limit
values of the second environment, Category C2:
The drive system is installed by appropriately qualified personnel in compliance with EMC
regulations - and the installation notes provided in the manual.
You use a shielded motor cable with low capacitance.
The pulse frequency is not higher than the value set in the factory.
The drive system is connected to a TN system.
The permissible motor cable length is complied with.
The current is not higher than the LO input current of the inverter (high-frequency, cable-
conducted interference voltages).
Specific technical data (Page 53).