Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
649
3 Function diagrams
3.10 Vector control / U/f control
Fig. 3-83 6490 – Speed control configuration
- 6490 -
Function diagram
87654321
fp_6490_97_01.vsd
Vector control / U/f control
G120 CU230P-2
13.03.2018 V4.7_10
Speed control configuration
...
00
[6040.3]
[6824.3]
[6040.3]
[6824.3]
n_reg Konfig
p1400[D]
[6030.6]
[6822.6]
...
05
...
15
19
20
21
Speed control configuration
Bit No. Meaning
1 = Automatic Kp/Tn adaptation active
Reserved
1 = Kp/Tn adaptation active
Reserved
1 = Acceleration model
1 = Sensorless vector control, speed pre-control active
Reserved
1 = Anti-windup for integral component
1 = Free Tn reduction active
[6031.4]
[6822.5]
<1>
Only with Power Module PM330.
<2>
Value range and/or factory setting depend on Power Module.
16
1 = I component for limiting enabled
...
Reserved
25
1 = Acceleration torque instantaneous in the I/f mode
<1>
<2>