Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
61
2 Parameters
2.2 List of parameters
Description: Sets the alarm threshold for the I2t power unit overload.
If this threshold is exceeded, an overload alarm is generated and the system responds as parameterized in p0290.
Dependency: Refer to: r0036, p0290
Refer to: A07805
Note: The I2t fault threshold is 100 %. If this value is exceeded, fault F30005 is output.
Description: Sets the fan run-on time after the pulses for the power unit have been canceled.
Note: - Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the excessively
high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
- for a PM230 power unit, sizes D - F the parameter is ineffective.
Description: Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency: Refer to: F30003
Description: Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency: Refer to: F30002
p0294 Power unit alarm with I2t overload / PU I2t alrm thresh
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8021
Min Max Factory setting
10.0 [%] 100.0 [%] 95.0 [%]
p0295 Fan run-on time / Fan run-on time
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [s] 600 [s] 0 [s]
r0296 DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [V] - [V] - [V]
r0297 DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8750, 8760, 8850,
8864, 8950, 8964
Min Max Factory setting
- [V] - [V] - [V]