Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
441
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the limit offset of the free technology controller 0.
Description: Sets the signal source to switch in/switch out the free technology controller 1.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
Description: Sets the unit for the parameters of the free technology controller 1.
Value: 1: %
2: 1 referred no dimensions
3: bar
4: °C
5: Pa
6: ltr/s
7: m³/s
8: ltr/min
9: m³/min
10: ltr/h
11: m³/h
12: kg/s
13: kg/min
14: kg/h
15: t/min
16: t/h
17: N
18: kN
19: Nm
20: psi
21: °F
22: gallon/s
23: inch³/s
24: gallon/min
25: inch³/min
26: gallon/h
27: inch³/h
28: lb/s
29: lb/min
30: lb/h
31: lbf
32: lbf ft
33: K
p11099 CI: Free tec_ctrl 0 limit offset signal source / Ftec0 lim offs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11100 BI: Free tec_ctrl 1 enable / Ftec1 enab
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11126 Free tec_ctrl 1 unit selection / Ftec1 unit sel
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(5) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
1 48 1