Operating Instructions

Defining the function of an analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog output via its index,
e.g. parameter p0771[0] is assigned to analog output 0.
Table 6-8 Connector outputs (CO) of the inverter (selection)
CO Significance CO Significance
r0021 Actual speed smoothed r0026 DC link voltage smoothed
r0024 Output frequency, smoothed r0027 Absolute actual current smoothed
r0025 Output voltage smoothed
A complete list of the connector outputs is provided in the List Manual.
Additional information is provided in the parameter list and in function diagram 2261 of the List
Manual.
Overview of the manuals (Page 538)
Application example: Defining the function of an analog output

$2
U
S>@
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current.
Set p0771 = 27.
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
Absolute-value generation of the signal (p0775)
Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 215