Installation Instructions

Table Of Contents
Installing/mounting
4
4.1 Installation conditions
General installation conditions
When installing the Power Modules, carefully observe the following sections in Chapter
Technical specifications (Page 57) in order to guarantee reliable, continuous and
disturbance-free operation.
Cable cross-sections and tightening torques
Electromagnetic compatibility
Ambient conditions
General technical data
The permissible fuses, power loss and the required cooling air quantities are listed in the
specific technical data
The EMC-compliant connection is described in Section:
EMC-compliant installation of a plant or machine (Page 23).
Inverters for plants and systems in the United States / Canada (UL/cUL)
To ensure a design that is in conformance with UL/cUL, only use the approved fuses
specified in Section "Technical data"
Detailed technical data (Page 64).
Only use copper conductors approved for 75°C.
The inverter features internal motor overload protection corresponding to UL508C. The
protection threshold is 115% of the inverter full load current. When commissioning, you can
adapt the motor overload protection using parameter p0640.
Additional requirements for CSA compliance
Install the inverter with a surge protection device with the following attributes:
Frame sizes FSA … FSC
Rated voltage 480 V (phase with respect to ground), 480 V (phase to phase)
Suitable for overvoltage category III
Suitable for SPD applications, type 1 or type 2
Terminal voltage, VPR = 2000 V
Power Module PM230, IP20 / Push-through technology (PT)
Hardware Installation Manual, 08/2016, A5E34331322B AB 21