Operating Instructions

List of parameters
Parameters
1-73
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the motor rotor resistance at an ambient temperature p0625.
Dependency: Refer to: p0625
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the nominal rotor resistance of the motor at the rated temperature.
The value is the sum of p0625 and p0628.
Dependency: Refer to: p0628
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the stator leakage inductance of the motor including the motor reactor (p0233).
Description: Displays the magnetizing inductance of the motor.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the rotor time constant.
Note: The parameter is not used for synchronous motors.
The value is calculated from the total of the inductances on the rotor side (p0358, p0360) divided by the rotor resis-
tance (p0354). The temperature adaptation of the rotor resistance for induction motors is not taken into account.
r0374[0...n] Motor rotor resistance cold / Mot R_r cold
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0376[0...n] Rated motor rotor resistance / Mot R_rotor rated
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0377[0...n] Motor leakage inductance total / Mot L_leak total
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [mH] - [mH] - [mH]
r0382[0...n] Motor magnetizing inductance transformed / Mot L_magn transf
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [mH] - [mH] - [mH]
r0384[0...n] Motor rotor time constant / damping time constant d axis / Mot T_rotor/T_Dd
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
- [ms] - [ms] - [ms]