Installation Instructions
Table Of Contents
- Power Module PM230, IP20 / Push-through technology (PT)
- Legal information - Warning notice system
- Table of contents
- 1 Changes in this manual
- 2 Fundamental safety instructions
- 3 Introduction
- 4 Installing/mounting
- 5 Connecting
- 6 Service and maintenance
- 7 Technical specifications
- 7.1 Overload capability of the inverter
- 7.2 Cable cross-sections and tightening torques
- 7.3 Electromagnetic compatibility - overview
- 7.4 Ambient conditions
- 7.5 General technical data
- 7.6 Detailed technical data
- 7.7 Restrictions for special ambient conditions
- 7.8 Electromagnetic compatibility of variable-speed drives
- 8 Spare parts and accessories
- A Appendix
- Index

4.2.3 Electromechanical components
Radio interference suppression
● Connect interference suppression elements to the following components:
– Coils of contactors
– Relays
– Solenoid valves
– Motor holding brakes
● Connect the interference suppression element directly at the coil.
● Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.
Installing/mounting
4.2 EMC-compliant installation of a plant or machine
Power Module PM230, IP20 / Push-through technology (PT)
28 Hardware Installation Manual, 08/2016, A5E34331322B AB