Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
619
3 Function diagrams
3.8 Internal control/status words
Fig. 3-56 2536 – Status word, monitoring functions 2 (r2198)
- 2536 -
Function diagram
87654321
fp_2536_97_01.vsd
Internal control/status words
G120 CU230P-2
13.03.2018 V4.7_10
Status word, monitoring functions 2 (r2198)
11
12
13
14
15
9
10
8
6
5
4
3
2
1
0
7
Status word, monitoring functions 2 (r2198)Bit No.
1 = |I_act| < I_threshold p2170
Reserved
Reserved
1 = |n_set| < p2161
1 = n_set > 0
1 = Motor blocked
1 = Motor stalled
1 = Load in the alarm range
1 = Load in the fault range
ZSW monitor 2
r2198
r2198
r2198.4
r2198.5
r2198.11
r2198.12
r2198.6
r2198.7
r2198.8
[8011.8]
[8011.8]
[8012.7]
[8012.8]
[8013.8]
[8013.8]
[8022.8]
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
[2530.2]
From speed signals
From speed signals
From torque messages, motor locked/stalled
From torque messages, motor locked/stalled
From load monitoring
From load monitoring
From monitoring functions