Operating Instructions
3 Function diagrams
3.8 Internal control/status words
SINAMICS G120 CU230P-2 Control Units
616 List Manual, 04/2018, A5E33838102
Fig. 3-53 2526 – Status word, closed-loop control (r0056)
- 2526 -
Function diagram
87654321
fp_2526_97_01.vsd
Internal control/status words
G120 CU230P-2
13.03.2018 V4.7_10
Status word, closed-loop control (r0056)
1
2
4
0
7
8
9
11
14
15
<1> [6722.3]
<2> [6835.5], [6837.3]
[6714.8]
[6833.8]
3
5
6
12
13
10
<4>
<4>
<4>
<5>
[6060.7]
[6826.8]
[6710.1]
[8012.5]
Only for U/f control.
Status word closed-loop control (r0056)Bit No.
1 = Initialization completed
1 = De-magnetization completed
1 = Pulse enable available
Reserved
1 = Magnetization completed
1 = Acceleration voltage active
1 = Frequency, negative
1 = Field weakening active
1 = Voltage limit active
1 = Slip limiting active
1 = Frequency limit active
1 = Current limiting controller, voltage output active
1 = Current/torque limiting active
1 = Vdc_max controller active
1 = Vdc_min controller active
ZSW cl-loop ctrl
r0056
r0056
1 = Starting boost active
r0056.0
r0056.1
r0056.4
r0056.5
r0056.11
r0056.12
r0056.2
r0056.6
r0056.9
r0056.13
r0056.14
r0056.15
r0056.7
r0056.8
r0056.10
Only for Power Modules PM230/PM240/PM330.<6>
<6>
[6031.6], [6710.2]
[6730.4], [6731.4], [6792.4]
[6841.4], [6842.4], [6843.4]
[6856.4]
[6730.4], [6731.4], [6792.4]
[6841.4], [6842.4], [6843.4]
[6856.4]
[6710.1]
<4>
[8012.5]
<6>
[6301.2]
[6851.2]
<1>
<2>
<3>
<1>
<2>
<3>
<1>
<3>
[6301.4]
[6851.5]
<1>
<3>
[6310.8]
[6853.8]
<1>
<3>
<1>
<2>
<3>
p0096 = 0: Expert
p0096 = 2: Dynamic Drive Control (DDC)
p0096 = 1: Standard Drive Control (SDC)
<1> [6220.8], [6320.8]
<2> [6827.8]
<3> [6854.8]
<1>
<3>
<1> [6220.8], [6320.8]
<2> [6827.8]
<3> [6854.8]
<1>
<2>
Only for vector control.<5>
<1> [6722.7]
<2> [6837.3]