Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
317
2 Parameters
2.2 List of parameters
Description: Sets the load monitoring configuration.
Value: 0: Monitoring switched out
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Monitoring load drop
4: Monitoring pump and load failure
5: Monitoring fan and load failure
Dependency: Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07891, A07892, A07893, F07894, F07895, F07896, A07920, A07921, A07922, F07923, F07924, F07925,
F07936
Note: p2193 = 4, 5 can only be combined with p2181 = 7, 8.
Description: Display and BICO output for the first status word of the monitoring functions.
Notice: For bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled
again as soon as the next pulse inhibit is present.
Note: For bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
For bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
For bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
For bit 04:
The threshold value is set in r1119 and the hysteresis in p2150.
For bit 05:
The threshold value is set in p1226 and the delay time in p1228.
p2193[0...n] Load monitoring configuration / Load monit config
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
0 5 1
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2534
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8022
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8022
05 |n_act| <= n_standstill p1226 Yes No 8022
06 |n_act| > n_max Yes No 8010
07 Speed setpoint - actual value deviation in
tolerance t_off
Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8022
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8022
10 Vdc_act > Vdc_threshold value p2172 Yes No 8022
11 Output load is not present Yes No 8022
13 |n_act| > n_max (F07901) Yes No -