Operating Instructions
Screw for functional grounding on the converter, frame size FSG
If you wish to use the inverters with integrated C3 line filter, please note the information in the
sections "TN line system", "TT line system" and "IT system" below.
Figure 4-9 Remove screw for functional grounding
4.4.1.1 TN line system
A TN line system transfers the PE protective
conductor to the installed plant or system us‐
ing a cable.
Generally, in a TN line system the neutral
point is grounded. There are versions of a TN
system with a grounded line conductor, e.g.
with grounded L1.
A TN line system can transfer the neutral con‐
ductor N and the PE protective conductor ei‐
ther separately or combined.
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH 6HSDUDWHWUDQVIHURI1DQG3(
JURXQGHGQHXWUDOSRLQW
/
/
/
1
3(
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 87