Operating Instructions

Select the appropriate application:
VEC STD: In all applications, which do not fit the other setting options.
PUMP FAN: Applications involving pumps and fans
SLVC 0HZ: Applications with short ramp-up and ramp-down times. However, this setting
is not suitable for hoisting gear and cranes/lifting gear.
PUMP 0HZ: Applications involving pumps and fans with optimized efficiency. The setting
only makes sense for steady-state operation with slow speed changes. We recommend
setting VEC STD if load surges in operation cannot be ruled out.
V LOAD: Applications with high breakaway torques, e.g. extruders, compressors and mills
The selection option depends on the Power Module being used. There is no selection option
for PM230 Power Modules.
Select the control mode:
VF LIN: U/f control with linear characteristic
VF LIN F: Flux current control (FCC)
VF QUAD: U/f control with square-law characteristic
SPD N EN: Encoderless vector control
3
7(&$33/
3
&75/02'
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Converter with the CU230P-2 Control Units
162 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF