Description: Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it
jumps directly to the voltage boost (p1350 = 0, Off).
Value: 0: OFF
1: ON
Note: The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
Description: Sets the configuration for the closed-loop speed control.
Note: Re bit 01:
When the bit is set, the I component of the speed controller is kept when changing into the open-loop controlled
mode.
p1350[0...n] Soft starting / Soft starting
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 1 0
p1400[0...n] Speed control configuration / n_ctrl config
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
- - 1000 0000 0010 0001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Automatic Kp/Tn adaptation active Yes No 6040
01 Sensorless vector control freeze I comp Yes No 6040
05 Kp/Tn adaptation active Yes No 6040
06 Free Tn adaptation active Yes No 6050
14 Torque pre-control Always active For n_ctrl enab 6060
15 Sensorless vector control, speed pre-control Yes No 6030