7.2 Cable cross-sections and tightening torques
Table 7-1 Connection, cross-section and tightening torque for PM230 Power Modules
Inverters Connection Cross-section, tightening torque Stripped
insulation
length
Metric Imperial
FSA Line supply, motor
Plug connector with
screw terminals
1 … 2.5 mm
2
, 0.5 Nm 16 … 14 AWG, 4.5 lbf in 8 mm
FSB 1.5 … 6 mm
2
, 0.6 Nm 16 … 10 AWG, 5.5 lbf in 8 mm
FSC 6 …16 mm
2
, 1.3 Nm 10 … 6 AWG, 12 lbf in 10 mm
FSD Line supply, motor
Cable lug
10 … 35 mm
2
, 6 Nm 7 … 2 AWG, 53 lbf in --
FSE 25 … 50 mm
2
, 6 Nm 3 … 1 AWG, 53 lbf in --
FSF 35 … 120 mm
2
, 13 Nm 2 … 4/0 AWG, 115 lbf in --
Technical specifications
7.2 Cable cross-sections and tightening torques
Power Module PM230, IP20 / Push-through technology (PT)
60 Hardware Installation Manual, 08/2016, A5E34331322B AB