Operating Instructions
Application examples
Pressure controlled supply fan + ESM fixed speed
7
85 |
118
Siemens
A5E36496664A_f
Smart Infrastructure 2021-10-11
7.4 Pressure controlled supply fan + ESM fixed
speed
● Macro 105 "Pressure controlled supply fan + ESM
fixed speed"
● Pressure in air duct regulated by integrated PID
controller
● Flying restart and automatic restart activated
● Essential service mode (in the event of fire) with
fixed frequency
● Error message: Digital output 0
● Status display: Digital output 2
When selecting this application using macro 105, the
technological unit remains unchanged at [%]. If
necessary, adapt the unit as described in the parameter
list. Select the values depending on the used sensor.
Notice:
In the case of the extended emergency mode, the
customer can no longer lodge any claims for warranty.
Extended emergency mode and the faults which arise
during this mode are logged in a password-protected
memory and can be read by the repair center.
Parameter Value Description
p596 500 Reference variable of the technological unit
p0010 5 Parameter filter change, technological unit
p595 5 Selection of technological unit: Pa
p0010 0 Parameter filter ready
p756[0] 0 Unipolar voltage input (0...10 V)
p0840 r722.0 ON / OFF (OFF1)
p1015[0] 1350 rpm Fixed speed setpoint 15
p1113[0] 0 Setpoint inversion
p1200[0] 1 Flying restart always active (start in setpoint direction)
p1210 26 Acknowledging all faults and restarting for an ON command
p2200[0] 1 Technology controller enable
p2201[0] 200 Pa Technology controller fixed value 1
p2253[0] p2201 Technology controller setpoint 1
p2257 30s Technology controller setpoint ramp-up time
p2258 30s Technology controller setpoint ramp-down time
p2264[0] r755[0] Technology controller actual value
p2265 10 s Technology controller actual value filter time constant
p2267 600 Pa Technology controller upper limit actual value
p2268 -50 Pa Technology controller lower limit actual value
p2293 30 s Technology controller ramp-up/ramp-down time
p3880 r722.1 ESM activation
p3881 1 ESM setpoint source: Fixed setpoint 15 (p1015)